WEB600 User’s Manual
4–20MA CURRENT LOOP TRANSDUCERS
The inputs on the Web600 are compatible with transducers that produce an analog output current of 4
to 20mA. Such transducers are available to measure tank and well levels, extreme temperatures, air pres-
sure, water pressure, flow, voltage, current, rotational speed, etc. Contact our technical support depart-
ment for assistance regarding your monitoring requirements. Follow the wiring diagrams below for
connecting a 4–20mA device:
External
24V
Power
Supply
FGD-0053
4-20 mA
Transducer
Wiring a 4–20mA device using an external 24 VDC supply.
RELAY OUTPUT WIRING
The WEB600 includes an SPST relay output that can be used to turn on a light, siren, or other device
whenever an alarm occurs. The output is a normally open dry contact that can be used for low voltage
switching. The relay is rated for up to 30VAC/VDC 1 Amp. A sample wiring diagram is shown below:
Ethernet
Power
Alarm
Zone
+1–
Zone
+6–
Zone
+5–
Zone
+4–
Zone
+3–
Zone
+2–
Relay
Output
The relay will engage whenever an input is above or below the programmed alarm limits and the pro-
grammed recognition time has been met. It will release as soon as the input returns to a normal condi-
tion.