Spot Water Detection Sensor
FGD-0013
v. 2.6
The Spot Water Detection Sensor will detect the presence of water at its probes. The Spot Water Detection
Sensor can be used with all models of Sensaphone
®
. The sensor is a normally closed (N.C.) device that is
polarity sensitive.
Wiring Instructions
1. Connect the red wire (positive) from the sensor to an alert input on the Sensaphone.
2. Connect the black wire (negative) to ground or common.
3. Configure your input normality as normally closed.
•Formodels400,800,1400,1800,2800:Press Set,then Configure to set normality.
•ForSensaphone2000,WEB600,SAT4D,SCADA3000,CELL682,andExpressII:Programtheinput
type as normally closed.
Consult your specific Sensaphone owner’s manual for further instructions.
4. Testthesensorbytouchingtheprobeswithadamppapertowel.
Installing Multiple Sensors
Multiplesensorsmaybeinstalledbywiringtheminseries,red(positive)toblack(negative).
TheFGD-0013ispoweredbyinternallithiumbatteries.Thebatteriesshouldlastforapproximately3-5
years.Whenthebatteriesstarttorundown,thesensorwillautomaticallycauseanalarmdialoutwhenno
water is present.
Specifications:
Normality:Normallyclosed
Dimensions:2.25"x1.125"x3.625"
Numberperinput:Multiple,wiredinseries
Battery Replacement:
1. Remove rubber feet from bottom.
2. Remove screws from under rubber feet only.
3. Open enclosure.
4. RemoveoldbatteriesandreplacewithtwoCR12253Vbatteries.
Fortechnicalsupport,call610-558-2700.